Installation - Electrical
18 CXRC-SVX01F-EN
Example:
L1 measured = 221 V
L2 measured = 230 V
L3 measured = 227 V
Note: L1 = 221 volts is the maximum deviation of the 3
voltages from the average of the 3 voltages.
Therefore, the imbalance percentage is:
The 2.2 % imbalance that exists in the example above
exceeds the maximum allowable imbalance between
phases.
221 + 230 + 227
= 226 volts
3
100 (226 – 221)
= 2.2%
226
Table 7. CCRC/CIRC Condenser electrical data
Tons Voltage
#
Fans
FLA
(ea.)
LRA
(ea.) MCA MCB
20, 29,
32
200 4 4.1 20.7 17.43 20
460 4 1.8 9 7.65 15
575 4 1.4 7.2 5.95 15
35, 40
200 6 4.1 20.7 25.63 30
460 6 1.8 9 11.25 15
575 6 1.4 7.2 8.75 15
50, 60
200 8 4.1 20.7 33.83 40
460 8 1.8 9 14.85 20
575 8 1.4 7.2 11.55 15
Note: All motors for CCRC/CIRC units are rated at 1 hp (0.7457 kW).