Trane Performance Air Handlers Manual de Instalação Página 13

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 20
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 12
CLCH-SVN05A-EN 13
Assembly and Installation
Pipe Cabinet Roof Curbs
Pipe cabinets ordered from Trane for field installation require special attention with regard to
joining the unit roof curb and pipe cabinet roof curb. A good joint will prevent any water
management problems within the pipe cabinet.
The pipe cabinet roof curb should be three-sided and have dimensions as shown in Figure 16, a
top view of the pipe cabinet roof curb, and Tab le 2. Dimension ‘L’ is from the outside of the unit roof
curb to the outside of the pipe cabinet roof curb. Dimension ‘X’ is the outside-to-outside width
dimension of the pipe cabinet roof curb. Dimension ‘Z’ locates the pipe chase roof curb along the
unit roof curb in the direction of airflow. This measurement is from the outside of the unit roof curb
to the outside of the pipe cabinet roof curb.
The basic formula becomes Z = LDS – 1, where LDS is the total length of the sections downstream
of the pipe cabinet.
Figure 16. Top view of unit and pipe cabinet roof curb Table 2. Pipe cabinet roof curb dimensions
Unit size
L dimension
Reduced Standard Extended
3 - 50 26.00 38.00 50.00
57-120 26.50 38.50 50.50
Unit sizes 3-120 X dimension
Reduced Lp + 3
Standard Lp + 3
Extended Lp + 3
Note: Lp is the sum of the section length(s) covered by the
pipe cabinet. Refer to submittal.
Unit roof curb
Pipe chase
roof curb
Z
X
L
Vista de página 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 19 20

Comentários a estes Manuais

Sem comentários