CLCH-SVN05A-EN 19
Assembly and Installation
• The first elbow in the ductwork leaving the unit should be no closer than 3 fan diameters from
the unit, thereby minimizing noise and resistance.
In those instances where the unit is installed over an acoustically critical area, additional treatment
of the ductwork is recommended. Both supply and return ductwork should be lined internally with
glass fiber duct liner 1-inch thick. The external surface of the supply duct should be covered with
an acoustical barrier material such as one or two pound/sq. ft. sheet lead (1/64-inch or 1/32-inch)
or loaded vinyl sheet or gypsum board for the first 10 ft. of ductwork. The lining should extend from
the point where the duct penetrates the roof to a distance of 10 ft. beyond the vertical drop from
the unit.