SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and
servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific
knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could
result in death or serious injury. When working on the equipment, observe all precautions in the literature
and on the tags, stickers, and labels that are attached to the equipment.
Installation, Operation
and Maintenance
Performance Climate Changer™ Air Handlers
Indoor and Outdoor Units
Sizes 3-120
October 2012
CLCH-SVX07C-EN
X-39641152010
Vista de página 0
1 2 3 4 5 6 ... 131 132

Resumo do Conteúdo

Página 1 - Installation, Operation

SAFETY WARNINGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating,

Página 2 - Environmental Concerns!

Pre-Installation Requirements10 CLCH-SVX07C-EN3. Notify your Trane sales representative of the damage and arrange for repair. Note: Do not attempt to

Página 3 - CLCH-SVX07C-EN 3

Installation - Electrical100 CLCH-SVX07C-ENField installed DDC control devices:• Install outside-air sensor and space sensor, if ordered.• Connect co

Página 4 - Table of Contents

Installation - ElectricalCLCH-SVX07C-EN 101 Quick ConnectsThe actuators, factory-mounted or field-supplied, are separately wired and controlled by a d

Página 5

Installation - Electrical102 CLCH-SVX07C-ENFigure 123. Typical VFD wiring schematic

Página 6 - Introduction

Installation - ElectricalCLCH-SVX07C-EN 103 Figure 124. Typical starter wiring schematic

Página 7 - General Information

104 CLCH-SVX07C-ENControls InterfaceThe portable operator display is used for temporary connection to and operation of Tracer MP580/581 controllers.

Página 8 - Required!

Controls InterfaceCLCH-SVX07C-EN 105 External communications portUnits with a factory-provided DDC controller can include a service module (see Figure

Página 9 - Pre-Installation Requirements

106 CLCH-SVX07C-ENStart-UpPre-Startup ChecklistOnce the air handler has been assembled and installed, attention must be directed to individual compon

Página 10 - Preparing the Unit Site

Start-UpCLCH-SVX07C-EN 107 Motor-Related Checks• Locate installation manual from the motor manufacturer for the specific motor installed. This can be

Página 11 - Microbial Growth!

Start-Up108 CLCH-SVX07C-EN.Table 32. Trane TR200 Switching FrequencyHorsepower Voltage Max KHz Trane Setting0.5 - 15 208/230 16 1620 - 25 208/230 14

Página 12 - Unit Dimensions and Weights

Start-UpCLCH-SVX07C-EN 109 Tension the Fan BeltProper belt tension is required to ensure maximum bearing and drive component life and is based on moto

Página 13

Pre-Installation RequirementsCLCH-SVX07C-EN 11 • Confirm the roof curb or foundation of the mounting platform is level and large enough to accommodat

Página 14

Start-Up110 CLCH-SVX07C-ENDetermine Fan SpeedFan speed can be determined using a strobe-type tachometer, or revolution counter.Check unit vibration i

Página 15

Start-UpCLCH-SVX07C-EN 111 Align Fan and Motor SheavesAlign the fan and motor sheaves using a straightedge. The straightedge must be long enough to s

Página 16

Start-Up11 2 CLCH-SVX07C-ENVCM (Transducer) Calibration.The VCM has an auto-zero function that recalibrates the transducer once every minute. When tr

Página 17

Start-UpCLCH-SVX07C-EN 11 3 Table 39. Back or top inlet low-flow Traq damper-air mixing and indoor economizer sectionsUnit Size Part NumberTraq Damper

Página 18

Start-Up114 CLCH-SVX07C-ENTable 41. Mixing box Traq damper inlet - single-side low flowUnit size Part numberTraq damper size (in)Damper type QtyPeak

Página 19

Start-UpCLCH-SVX07C-EN 11 5 Table 43. Mixing box Traq damper inlet - dual-side low-flowUnit size Part numberTraq damper size (in) Damper type QtyPeak

Página 20 - Fans/Motors

Start-Up11 6 CLCH-SVX07C-ENTable 45. Side inlet low-flow Traq dampers - diagonal economizer section Unit size Part numberTraq damper size (in)Damper

Página 21 - Installation - Mechanical

Start-UpCLCH-SVX07C-EN 11 7 Fan Inlet Airflow Measuring SystemA fan inlet airflow measuring system is available on many centrifugal and plenum fans. E

Página 22

Start-Up11 8 CLCH-SVX07C-ENConstant Factor KThe constant factor K is unique for each fan and is primarily a function of the area and other geometric

Página 23

Start-UpCLCH-SVX07C-EN 119 When a single transmitter is supplied in a multiple fan system, one or more fans will be brought back to the transmitter a

Página 24

12 CLCH-SVX07C-ENUnit Dimensions and WeightsService ClearancesA minimum clearance of the section width plus 12 inches on the access door side of the

Página 25 - Unit Placement and Assembly

Start-Up120 CLCH-SVX07C-ENField-obtained factors can provide maximum accuracy. To obtain the factor in the field, measure the differential pressure o

Página 26 - Risk of Unit Dropping!

CLCH-SVX07C-EN 121 Routine MaintenanceWARNINGHazardous Service Procedures!The maintenance and troubleshooting procedures recommended in this manual co

Página 27 - Hole diameter

Routine Maintenance122 CLCH-SVX07C-ENAir FiltersThrowaway FiltersTo replace throwaway filters, install new filters with the directional arrows pointi

Página 28

Routine MaintenanceCLCH-SVX07C-EN 123 8. Be careful any contaminated material does not contact other areas of the unit or building. Properly dispose o

Página 29 - CLCH-SVX07C-EN 29

Routine Maintenance124 CLCH-SVX07C-ENTorque RequirementsRefer to Tab le 48 for minimum torque of motor mounting and bearings bolts. Refer to Table 35

Página 30

Routine MaintenanceCLCH-SVX07C-EN 125 CoilsAll coils should be kept clean to maintain maximum performance.Steam and Water CoilsTo clean steam and wate

Página 31

Routine Maintenance126 CLCH-SVX07C-ENTo clean refrigerant coils:1. Disconnect all electrical power to the unit.2. Wearing the appropriate personal pr

Página 32 - Butyl tape

Routine MaintenanceCLCH-SVX07C-EN 127 Providing a moisture purge cycle 15 to 30 minutes after shutdown disperses the cold, humid air inside the air-ha

Página 33

Routine Maintenance128 CLCH-SVX07C-ENUltraviolet (UV) Light MaintenanceThe intensity of the ultraviolet energy emitted from the ultraviolet bulbs is

Página 34 - Stacked Outdoor Units

CLCH-SVX07C-EN 129 TroubleshootingThis section is intended to be used as a diagnostic aid only. For detailed repair procedures, contact your local Tra

Página 35 - Unit assembly

Unit Dimensions and WeightsCLCH-SVX07C-EN 13 Table 4. Section dimensions (inches) and weights (pounds) - unit sizes 3-30Nominal airflow 1500 2000 3000

Página 36

Troubleshooting130 CLCH-SVX07C-ENShort belt lifeWorn sheaves Replace sheaves.Misaligned belt Realign drive with MVP sheave set at mean pitch diamet

Página 37 - Flashing Installation

TroubleshootingCLCH-SVX07C-EN 131

Página 38

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, theleader in creating and sustaining safe, comf

Página 39 - Detail C

Unit Dimensions and Weights14 CLCH-SVX07C-ENUnit size3 4 6 8 10 12 14 17 21 22 25 26 30Diffuser10.00 10.00 10.00 14.00 14.00 14.00 14.00 14.00 14.00

Página 40 - Flashing Installation Notes

Unit Dimensions and WeightsCLCH-SVX07C-EN 15 Unit size3 4 6 8 10 12 14 17 21 22 25 26 30Gas heat- 200 MBH n/a n/a57.00 57.00 59.00 57.00 57.00 60.00 6

Página 41 - Install flashing and hood

Unit Dimensions and Weights16 CLCH-SVX07C-ENSections below are for outdoor units onlyUnit size3 4 6 8 10 12 14 17 21 22 25 26 30Diagonal economizer -

Página 42 - Assembly

Unit Dimensions and WeightsCLCH-SVX07C-EN 17 Unit size31 35 36 40 41 50 51 57 58 66 80 100 120-Ducted inlet or ducted outlet section10.00 10.00 10.00

Página 43

Unit Dimensions and Weights18 CLCH-SVX07C-ENUnit size31 35 36 40 41 50 51 57 58 66 80 100 120-Direct-drive plenum fan with motor73.25 63.75 80.50 63.

Página 44 - External Raceway Assembly

Unit Dimensions and WeightsCLCH-SVX07C-EN 19 Unit size31 35 36 40 41 50 51 57 58 66 80 100 120Mixing box-with angled filters46.00 48.00 46.00 48.00 46

Página 45 - Filter Section

© 2012 Trane All rights reserved CLCH-SVX07C-ENWarnings, Cautions and NoticesWarnings, Cautions and Notices.Note that warnings, cautions and notice

Página 46 - Filter Placement

Unit Dimensions and Weights20 CLCH-SVX07C-ENFans/MotorsStarter/VFD WeightsFan weights do not include starter/VFD weights. Table 6 gives approximate s

Página 47 - CLCH-SVX07C-EN 47

CLCH-SVX07C-EN 21 Installation - MechanicalLifting and RiggingRemove Shipping Tie-DownsPrior to unit placement, remove the shipping tie-downs. See Fig

Página 48 - 48 CLCH-SVX07C-EN

Installation - Mechanical22 CLCH-SVX07C-EN• Access for removal of shipping tie-downs for unit sizes 3-30 is available through the fan section access

Página 49 - CLCH-SVX07C-EN 49

Installation - MechanicalCLCH-SVX07C-EN 23 • For unit sizes 3 to 120 with integral base frame, use field-provided spreader bars and slings to rig unit

Página 50 - 50 CLCH-SVX07C-EN

Installation - Mechanical24 CLCH-SVX07C-ENLifting Hoods and Pipe CabinetsForklifting ConsiderationsNote: Do not use a forklift on outdoor air handler

Página 51 - CLCH-SVX07C-EN 51

Installation - MechanicalCLCH-SVX07C-EN 25 Unit Placement and AssemblyIf the air handler ships in subassemblies or in individual sections, some assemb

Página 52 - 52 CLCH-SVX07C-EN

Installation - Mechanical26 CLCH-SVX07C-ENFor proper operation, the unit must be installed level (zero tolerance) in both horizontal axes. For vertic

Página 53 - CLCH-SVX07C-EN 53

Installation - MechanicalCLCH-SVX07C-EN 27 Using Integral Base FrameIf using the factory-provided integral base frame for ceiling suspension, individu

Página 54 - 54 CLCH-SVX07C-EN

Installation - Mechanical28 CLCH-SVX07C-EN4. If the unit is equipped with factory-mounted controls, move adjacent subassembly within six inches and f

Página 55 - CLCH-SVX07C-EN 55

Installation - MechanicalCLCH-SVX07C-EN 29 is to raise one end of the shipping section to clear the hemming before pulling the units together. 9. In a

Página 56 - 56 CLCH-SVX07C-EN

Warnings, Cautions and NoticesCLCH-SVX07C-EN 3 Ultraviolet (UV) Germicidal Irradiation Lights!The United States Environmental Protection Agency (EPA)

Página 57

Installation - Mechanical30 CLCH-SVX07C-EN10. For unit sizes 3-30, bolt the unit base frames together using 5/16-inch bolts (see Figure 29).11. For u

Página 58

Installation - MechanicalCLCH-SVX07C-EN 31 14. Install the section-to-section screws inserting the appropriate screws through the overlapping flanges

Página 59

Installation - Mechanical32 CLCH-SVX07C-ENPipe Cabinet Installation 1. After air handler is completely installed and checked for accuracy of level an

Página 60

Installation - MechanicalCLCH-SVX07C-EN 33 9. Install inside corner cap. See Figure 33 Detail A and B.10. Install 3/8-inch x 3/8-inch white butyl tape

Página 61

Installation - Mechanical34 CLCH-SVX07C-ENOutdoor Unit Weather Hoods1. Per the unit drawing determine mounting location of the unit weather hoods.2.

Página 62 - Fan Section

Installation - MechanicalCLCH-SVX07C-EN 35 Unit assembly1. See Figure 35. Apply gasket (Item 1) on top of lower unit. Compress gasketing to ensure a g

Página 63 - Requirements

Installation - Mechanical36 CLCH-SVX07C-ENVertical Seam Cap Installation1. See Figure 36. Apply ribbed Butyl tape (Item 6) over all vertical shipping

Página 64 - Hurricane Application

Installation - MechanicalCLCH-SVX07C-EN 37 Flashing InstallationFor additional information, see “Flashing Installation Notes” on page 40.For hood inst

Página 65 - Hurricane Unit Anchorage

Installation - Mechanical38 CLCH-SVX07C-ENFigure 38. Flashing installation locationDetail ABase rail.060 gap betweenbottom of panel andtop of flashin

Página 66 - Gas Heat Installation

Installation - MechanicalCLCH-SVX07C-EN 39 Figure 40. Flashing for corner seamsAssembled viewDetail CApply caulk(14) Adhesive/sealant:Flex polyurethan

Página 67 - Pipe Cabinet Installation

4 CLCH-SVX07C-ENTable of ContentsWarnings, Cautions and Notices . . . . . . . . . . 2Introduction . . . . . . . . . . . . . . . . . . . . . . . . .

Página 68 - 68 CLCH-SVX07C-EN

Installation - Mechanical40 CLCH-SVX07C-ENFlashing Installation Notes• Side flashing will have locating features:– Right side front and back pieces w

Página 69 - Damper Section

Installation - MechanicalCLCH-SVX07C-EN 41 Install flashing and hood1. See Figure 43. Secure two hood support brackets (Item 15) to base rail with scr

Página 70 - Damper Torque Requirements

Installation - Mechanical42 CLCH-SVX07C-ENIndoor Dual-Path SDU/Winterizer AssemblyA dual-path, Split Dehumidification Unit (SDU)/winterizer air handl

Página 71 - CLCH-SVX07C-EN 71

Installation - MechanicalCLCH-SVX07C-EN 43 5. Install screws as shown in Figure 46 inserting the appropriate screws using a powered impact gun and tak

Página 72 - 72 CLCH-SVX07C-EN

Installation - Mechanical44 CLCH-SVX07C-ENExternal Raceway AssemblyFor air handling units with factory-installed power wiring extending from the firs

Página 73 - CLCH-SVX07C-EN 73

Component Installation RequirementsCLCH-SVX07C-EN 45 Component Installation RequirementsThe components in the air handler may have installation requir

Página 74 - 74 CLCH-SVX07C-EN

Component Installation Requirements46 CLCH-SVX07C-ENFilter PlacementFigure 53. 2-inch and 4-inch flat filter placement for unit sizes 3-50 - side loa

Página 75 - CLCH-SVX07C-EN 75

Component Installation RequirementsCLCH-SVX07C-EN 47 Figure 54. 2-inch and 4-inch flat filter placement for unit sizes 51-120 - side loadingSize 51122

Página 76 - 76 CLCH-SVX07C-EN

Component Installation Requirements48 CLCH-SVX07C-ENFigure 55. 2-inch/4-inch combination flat filter placement for unit sizes 3-50 - side loadingSize

Página 77 - CLCH-SVX07C-EN 77

Component Installation RequirementsCLCH-SVX07C-EN 49 Figure 56. 2-inch/4-inch combination flat filter placement for unit sizes 51-120 - side loadingSi

Página 78 - 78 CLCH-SVX07C-EN

CLCH-SVX07C-EN 5 Table of ContentsBottom Opening Duct Installation . . . . . . 81Discharge Plenum Connections . . . . . . . 82Bell Mouth Discharge

Página 79 - Duct Connections

Component Installation Requirements50 CLCH-SVX07C-ENFigure 57. 2-inch and 4-inch angled filter placement for unit sizes 3-50 - side loadingSize 31625

Página 80 - Damper Connections

Component Installation RequirementsCLCH-SVX07C-EN 51 Figure 58. 2-inch and 4-inch angled filter placement for unit sizes 51-120 - side loadingSize 512

Página 81 - CLCH-SVX07C-EN 81

Component Installation Requirements52 CLCH-SVX07C-ENFigure 59. Long bag filter placement for unit sizes 3-50 - side loadingSize 320243.9Size 42020 .8

Página 82 - Discharge Plenum Connections

Component Installation RequirementsCLCH-SVX07C-EN 53 Figure 60. Long bag filter placement for unit sizes 57-120 - side loadingSize 51242424 24 12 7.12

Página 83 - Traq Damper Connections

Component Installation Requirements54 CLCH-SVX07C-ENFigure 61. Short bag filter placement for unit sizes 3-50 - side loadingSize 320243.9Size 42020 .

Página 84 - 84 CLCH-SVX07C-EN

Component Installation RequirementsCLCH-SVX07C-EN 55 Figure 62. Short bag filter placement for unit sizes 57-120 - side loadingSize 51242424 24 12 7.1

Página 85 - Other Connections

Component Installation Requirements56 CLCH-SVX07C-ENFigure 63. Cartridge filter placement for unit sizes 3-50 - side loadingSize 320243.9Size 42020 .

Página 86 - Coil Piping and Connections

Component Installation RequirementsCLCH-SVX07C-EN 57 Figure 64. Cartridge filter placement for unit sizes 57-120 - side loadingSize 51242424 24 12 7.1

Página 87 - Steam Coil Piping

Component Installation Requirements58 CLCH-SVX07C-ENFigure 65. Front-load bag and cartridge filter placement for unit size 3-50Size 312243.38Size 412

Página 88 - Coil Condensate!

Component Installation RequirementsCLCH-SVX07C-EN 59 Figure 66. Front-loading bag and cartridge filter placement for unit size 57-120Size 512424 24 12

Página 89 - Water Coil Piping

6 CLCH-SVX07C-ENIntroductionOverview of ManualUse this manual to install, startup, operate, and maintain the Performance Climate Changer™ air handler

Página 90

Component Installation Requirements60 CLCH-SVX07C-ENFigure 67. HEPA filter placement for unit size 3-50 - front loadingSize 312242.88Size 41224 15.38

Página 91 - Valve Damage!

Component Installation RequirementsCLCH-SVX07C-EN 61 Figure 68. HEPA filter placement for unit size 57-120 - front loadingSize 51301230 24 3.625242424

Página 92 - Suction Lines

Component Installation Requirements62 CLCH-SVX07C-ENFan SectionThe fan section can be configured as either draw-thru or blow-thru. Review the submitt

Página 93

Component Installation RequirementsCLCH-SVX07C-EN 63 Seismic Application RequirementsAir handling equipment manufactured by Trane is capable of struct

Página 94

Component Installation Requirements64 CLCH-SVX07C-ENHurricane Application RequirementsMiami/Dade County Hurricane-Certified Air HandlersPerformance C

Página 95

Component Installation RequirementsCLCH-SVX07C-EN 65 Hurricane Unit AnchorageFigure 76. Typical direct anchorage to substrate at lifting lugs (also se

Página 96

Component Installation Requirements66 CLCH-SVX07C-ENGas Heat InstallationFigure 79. Installation of front and back hoodsItem Description123Support br

Página 97

Component Installation RequirementsCLCH-SVX07C-EN 67 Pipe Cabinet InstallationNested U Channels and L angle have to be removed to install the pipe cab

Página 98

Component Installation Requirements68 CLCH-SVX07C-EN4. Attach the unit base L angle from the pipe cabinet to the unit base rail. See Step 4 in Figure

Página 99

Component Installation RequirementsCLCH-SVX07C-EN 69 Pipe Cabinet Hurricane AnchorageDamper SectionDampers are factory-installed and adjusted and can

Página 100 - Installation - Electrical

General InformationCLCH-SVX07C-EN 7 General InformationOperating EnvironmentThe Performance Climate Changer™ air handler is a central station air hand

Página 101 - Quick Connects

Component Installation Requirements70 CLCH-SVX07C-ENDamper Torque RequirementsTable 12. Mixing box damper torque requirements (inch pound) at 1-inch

Página 102

Component Installation RequirementsCLCH-SVX07C-EN 71 Table 14. Air-to-Air Plate Heat Exchanger Frost DamperUnit size A B Damper qtyDamper torque (in-l

Página 103

Component Installation Requirements72 CLCH-SVX07C-ENTable 17. Single -Side Traq low flow mixing boxUnit sizeDamper Dia (in)Damper QtyDamper

Página 104 - Controls Interface

Component Installation RequirementsCLCH-SVX07C-EN 73 Table 20. Side rectangle angle damper - 2000 fpmUnit size A (in) B (in)Damper qtyTorque (in-lb.)A

Página 105 - External communications port

Component Installation Requirements74 CLCH-SVX07C-ENTable 22. Short mixing box rectangle damper - top, back or bottom onlyUnit size A (in) B (in) Dam

Página 106 - Start-Up

Component Installation RequirementsCLCH-SVX07C-EN 75 Table 24. Energy recovery bypass opposed-blade damperUnit size A (in) B (in)Damper qtyTorque (in-

Página 107 - Unit Operation

Component Installation Requirements76 CLCH-SVX07C-ENTable 26. Energy recovery recirculation parallel-blade damperUnit size A (in) B (in)Damper qtyTor

Página 108

Component Installation RequirementsCLCH-SVX07C-EN 77 Table 28. Internal face-and-bypass damper torque requirementsUnit size A (in) B (in) Damper Qty T

Página 109 - Belt Tension! (2 of 2)

Component Installation Requirements78 CLCH-SVX07C-ENUnit size A (in) B (in)Damper QtyBypass Torque (in-lb)Face Torque (in-lb.)Torque (in-lb)Actuator

Página 110 - Live Electrical Components!

Component Installation RequirementsCLCH-SVX07C-EN 79 Multizone ModulesUnder certain operating conditions, condensation may form on the cold deck porti

Página 111 - Traq™ Dampers

General Information8 CLCH-SVX07C-ENFor a more in-depth understanding of controls, refer to the following manuals:• For programmable MP580 controllers

Página 112

Component Installation Requirements80 CLCH-SVX07C-ENConnections made directly to the discharge opening of a housed fan should have a minimum of three

Página 113

Component Installation RequirementsCLCH-SVX07C-EN 81 Bottom Opening Duct Installation1. Install gasket to duct flange to ensure air tight seal.2. Inst

Página 114

Component Installation Requirements82 CLCH-SVX07C-ENDischarge Plenum ConnectionsDischarge plenum sections are available with or without openings. Sec

Página 115

Component Installation RequirementsCLCH-SVX07C-EN 83 Traq Damper ConnectionsSize the duct connections to attach to the specified portion on the face o

Página 116

Component Installation Requirements84 CLCH-SVX07C-ENExternal Face-and-Bypass ConnectionsThe external face-and-bypass damper sections will require a f

Página 117 - Transmitter Calibration

Component Installation RequirementsCLCH-SVX07C-EN 85 Other ConnectionsAccess, filter, and other sections may have open inlets with a 2-inch (sizes 3-1

Página 118 - Constant Factor K

86 CLCH-SVX07C-ENCoil Piping and ConnectionsGeneral RecommendationsProper installation, piping, and trapping is necessary to ensure satisfactory coil

Página 119

Coil Piping and ConnectionsCLCH-SVX07C-EN 87 Steam Coil PipingAir handlers fitted with steam coils have labeled holes for piping penetrations. Figure

Página 120 - Maintenance

Coil Piping and Connections88 CLCH-SVX07C-ENTo prevent coil damage, complete the following recommendations:• Install a 1/2-inch NPT, 15 degree swing

Página 121 - Routine Maintenance

Coil Piping and ConnectionsCLCH-SVX07C-EN 89 Water Coil Piping Figure 105, and Figure 106 illustrate typical water coil piping configurations.Type 5A,

Página 122 - Drain Pans

CLCH-SVX07C-EN 9 Pre-Installation RequirementsBased on customer requirements, Trane air handlers can ship as complete units or as individual sections

Página 123 - Rotating Components!

Coil Piping and Connections90 CLCH-SVX07C-ENRefrigerant Coil PipingNote: Refer to for information on handling refrigerants.Use Figure 108 to determi

Página 124

Coil Piping and ConnectionsCLCH-SVX07C-EN 91 Liquid LinesLine SizingProperly sizing the liquid line is critical to a successful split-system applicati

Página 125

Coil Piping and Connections92 CLCH-SVX07C-ENSuction LinesLine sizingProper suction-line sizing is required to guarantee the oil returns to the compre

Página 126 - Coil Freeze-up!

Coil Piping and ConnectionsCLCH-SVX07C-EN 93 1. Pitch the liquid line slightly—1 inch/10 feet —so that the refrigerant drains toward the evaporator.2.

Página 127

Coil Piping and Connections94 CLCH-SVX07C-ENFigure 111. Single-circuit condensing unit: evaporator coil with two distributors1. Pitch the liquid line

Página 128 - Ultraviolet (UV) Light

Coil Piping and ConnectionsCLCH-SVX07C-EN 95 Figure 112. Single-Circuit Condensing Unit: Evaporator Coil with Four Distributors1. Pitch the liquid lin

Página 129 - Troubleshooting

Coil Piping and Connections96 CLCH-SVX07C-EN1. Pitch the liquid lines slightly—1 inch/10 feet —so the refrigerant drains toward the evaporator.2. Pro

Página 130

Coil Piping and ConnectionsCLCH-SVX07C-EN 97 Figure 114. Dual-circuit condensing unit: evaporator coil with four distributors1. Pitch the liquid line

Página 131

Coil Piping and Connections98 CLCH-SVX07C-ENFigure 115.Dual-circuit condensing unit: evaporator coil with eight distributors1. Pitch the liquid line

Página 132

CLCH-SVX07C-EN 99 Installation - Electrical.Units intended for indoor use are available with starters or variable-frequency drives (VFDs) that are ext