Trane Variable Refrigerant Flow System Mini Outdoor Unit Series Manual de Instalação

Consulte online ou descarregue Manual de Instalação para Aparelhos de ar condicionado "split system" Trane Variable Refrigerant Flow System Mini Outdoor Unit Series. Trane Variable Refrigerant Flow System Mini Outdoor Unit Series Installation and Maintenance Manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 52
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 0
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and
servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific
knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could
result in death or serious injury. When working on the equipment, observe all precautions in the literature
and on the tags, stickers, and labels that are attached to the equipment.
May 2013 VRF-SVN33A-EN
Installation
Variable Refrigerant Flow (VRF) System
Mini Outdoor Unit Series
Models:
4TVH0036B100NB
4TVH0048B100NB
4TVH0053B100NB
Vista de página 0
1 2 3 4 5 6 ... 51 52

Resumo do Conteúdo

Página 1 - Installation

SAFETY WARNINGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating,

Página 2 - Introduction

10 VRF-SVN33A-ENFigure 4. Moving the mini outdoor unitUnit InstallationFollow these guidelines for installing the mini outdoor unit.Important: The man

Página 3 - Table of Contents

VRF-SVN33A-EN 11Unit InstallationMinimizing VibrationWhen installing multiple mini outdoor units side by side, or when there is a need to minimize uni

Página 4 - 4 VRF-SVN33A-EN

12 VRF-SVN33A-ENUnit InstallationFigure 7. Anchor bolt positionsIf you cannot attach the unit to the base or if the unit needs additional support, se

Página 5 - Preparing for Installation

VRF-SVN33A-EN 13Refrigerant PipingRefrigerant PipingThis section contains information on selecting, storing, and connecting refrigerant piping.Selecti

Página 6

14 VRF-SVN33A-ENRefrigerant PipingBranch Joint SelectionTable 5 specifies the first branch joint according to mini outdoor unit capacity. Table 6 spe

Página 7 - Service Clearances

VRF-SVN33A-EN 15Refrigerant PipingRefrigerant Piping Maximum Length and Height Differences Figure 9. Y-joint connection Figure 10. Y-joint and EEV kit

Página 8 - Location Considerations

16 VRF-SVN33A-ENRefrigerant PipingFigure 11. Distribution header connectionTable 9. Maximum refrigerant piping length and height differences for inst

Página 9 - Moving the Mini Outdoor Unit

VRF-SVN33A-EN 17Refrigerant PipingFigure 12. Y-joint and distribution header connection Storing Refrigerant PipingTo prevent foreign materials or wate

Página 10 - Unit Installation

18 VRF-SVN33A-ENRefrigerant PipingInstalling Refrigerant Piping Overview1. Cut or extend field-supplied piping as needed. To extend pipes, braze or

Página 11 - Minimizing Vibration

VRF-SVN33A-EN 19Refrigerant PipingNitrogen Flushing While BrazingWhile brazing refrigerant pipes, flush them with nitrogen gas. Use a pressure regulat

Página 12 - Sharp Edges!

2 VRF-SVN33A-ENIntroductionRead this manual thoroughly before operating or servicing this unit.Warnings, Cautions, and NoticesSafety advisories appea

Página 13 - Refrigerant Piping

20 VRF-SVN33A-ENRefrigerant Piping3. Attach the yoke to the flaring bar, centering the conical part over the end of the pipe that is extending above

Página 14 - Risk of Pipes Breaking!

VRF-SVN33A-EN 21Refrigerant PipingConnecting Piping to the Mini Outdoor UnitImportant: Ensure that all pipe connections are accessible for servicing a

Página 15

22 VRF-SVN33A-ENRefrigerant Piping4. After making electrical connections (see “Electrical Wiring” p. 23) and insulating the pipes (see “Insulating Re

Página 16

VRF-SVN33A-EN 23Electrical WiringElectrical WiringObserve the following precautions when making electrical connections. Refer to wiring diagrams (Figu

Página 17 - Evacuating Refrigerant

24 VRF-SVN33A-ENElectrical WiringFigure 16. Typical system installation wiring with external EEV kitGroundPower cablecircuit breaker or disconnectCom

Página 18 - Installing Refrigerant Piping

VRF-SVN33A-EN 25Electrical WiringPower Wiring• Multi-pole circuit breaker or disconnect is required to fully isolate the unit from all power. • Instal

Página 19 - Avoid Unit Damage!

26 VRF-SVN33A-ENElectrical Wiring2. Cut the power cable to an appropriate length and connect it to terminals L and N in the power supply box with a s

Página 20

VRF-SVN33A-EN 27Electrical WiringGroundingImportant: Grounding must be done by a qualified electrician. The unit cannot be ground by a gas or water pi

Página 21

28 VRF-SVN33A-ENElectrical Wiring• If you have grounded the unit to a grounding terminal or electrical panel, ensure that the resistance meets the re

Página 22

VRF-SVN33A-EN 29Leak Testing Pipe ConnectionsLeak Testing Pipe ConnectionsBefore leak testing pipe connections, read all safety precautions and notes.

Página 23 - Electrical Wiring

Table of ContentsVRF-SVN33A-EN 3Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Página 24

30 VRF-SVN33A-ENLeak Testing Pipe ConnectionsUse the following procedure for leak testing pipe connections. 1. Connect the refrigerant manifold gauge

Página 25 - Power Wiring

VRF-SVN33A-EN 31Vacuum Drying ProcedureAfter performing a successful leak test, follow this vacuum drying procedure:Notes:• Use tools rated for R-410A

Página 26

32 VRF-SVN33A-ENInsulating Refrigerant PipesInsulating Refrigerant PipesAfter determining that there are no leaks in the refrigerant pipes, insulate

Página 27 - Grounding

VRF-SVN33A-EN 33Insulating Refrigerant Pipes• Overlap insulation to avoid gaps.• Avoid compressing the insulation as much as possible.• Be sure there

Página 28 - Communications Wiring

34 VRF-SVN33A-ENRefrigerantRefrigerantAfter successful leak testing and vacuum drying, calculate the amount of refrigerant needed and then charge the

Página 29 - Leak Testing Pipe Connections

VRF-SVN33A-EN 35RefrigerantCharging the RefrigerantAfter calculating the correct amount of refrigerant needed by the system (see “Calculating the Refr

Página 30 - Refrigerant Pipe Damage!

36 VRF-SVN33A-ENConnecting the Drain HoseConnecting the Drain HoseWhen using the air conditioner in the heating mode, ice may accumulate. When the un

Página 31 - Vacuum Drying Procedure

VRF-SVN33A-EN 37Control SystemControl SystemThe control board contains a 7-segment display, three DIP switches, two rotary switches, and four buttons,

Página 32 - Insulating Refrigerant Pipes

38 VRF-SVN33A-ENControl SystemConfiguring the SystemThe control board contains two rotary switches and three DIP switches (shown in Figure 22). The f

Página 33

VRF-SVN33A-EN 39Control SystemTable 20. Configuration using DIP switches K9–K12DIP switch Setting Function descriptionNight-time silent mode(a)(a) Red

Página 34 - Refrigerant

4 VRF-SVN33A-ENVacuum Drying Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Insulating Refri

Página 35 - Charging the Refrigerant

40 VRF-SVN33A-ENControl SystemTable 21. System configuration using DIP switches K13–K16DIP switchMaximum current per unit model4TVH0036B100NB 3 ton4T

Página 36 - Connecting the Drain Hose

VRF-SVN33A-EN 41Control SystemInitiating System OperationsButtons K1, K2, and K3 are used to initiate system operations. The first two digits of the 7

Página 37 - Control System

42 VRF-SVN33A-ENControl SystemMonitoring System SettingsButtons K4 is used to monitor system settings and software versions. Table 25. Button K4Numb

Página 38 - Configuring the System

VRF-SVN33A-EN 43Pre-Start ChecksPre-Start ChecksAfter installation and before the test operation is conducted, perform the following pre-start checks:

Página 39

44 VRF-SVN33A-ENTest OperationTest OperationAfter all pre-start checks (refer to “Pre-Start Checks” p. 43) have been have been completed, run the tes

Página 40

VRF-SVN33A-EN 45Test OperationNote: When power is supplied to the outdoor unit, it will check for and verify communications with the indoor units.2. E

Página 41 - Initiating System Operations

46 VRF-SVN33A-ENRefrigerant detection operationRefrigerant detection operationPerform the refrigerant detection operation only under the following co

Página 42 - Monitoring System Settings

VRF-SVN33A-EN 47Service: Pump Down ProcessService: Pump Down ProcessThe pump down process pulls all of the refrigerant in the system into the outdoor

Página 43 - Pre-Start Checks

48 VRF-SVN33A-ENService: Pump Down ProcessPump Down Process1. Follow the procedure for “Collecting Refrigerant into a Refrigerant Container” p. 47”.2

Página 44 - Test Operation

VRF-SVN33A-EN 49Warranty For Trane Advantage™ VRF Systems and Related AccessoriesWarranty For Trane Advantage™ VRF Systems and Related AccessoriesProd

Página 45

VRF-SVN33A-EN 5Preparing for InstallationPreparing for InstallationUnit Dimensions and Weights Dimensional Drawing Table 1. Unit dimensions and weight

Página 46 - 46 VRF-SVN33A-EN

50 VRF-SVN33A-ENWarranty For Trane Advantage™ VRF Systems and Related Accessories

Página 48 - Pump Down Process

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, com

Página 49 - Related Accessories

6 VRF-SVN33A-ENPreparing for InstallationMaximum Quantity of Indoor Units by Mini Outdoor Unit CapacityTo prevent reducing indoor unit capacity, the

Página 50 - 50 VRF-SVN33A-EN

VRF-SVN33A-EN 7Preparing for InstallationService ClearancesInstall units as shown in the illustrations below (Figure 1, Figure 2, and Figure 3), obser

Página 51

8 VRF-SVN33A-ENPreparing for InstallationFigure 3. Minimum service clearances for multiple mini outdoor unit installationsLocation ConsiderationsChoo

Página 52

VRF-SVN33A-EN 9Preparing for Installationcirculation. Consult an installation expert about taking anti-corrosion measures, such as removing salinity o

Comentários a estes Manuais

Sem comentários