Trane Variable Refrigerant Flow System Mini Outdoor Unit Series Manual de Instalação Página 41

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 52
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 40
VRF-SVN33A-EN 41
Control System
Initiating System Operations
Buttons K1, K2, and K3 are used to initiate system operations. The first two digits of the 7-segment
display respond as shown in the last column of the following tables.
Table 22. Button K1
Number of times K1
is pressed Operation
7-segment display:
Digits 1 and 2
1 (hold for 5 seconds) Test operation
1
Refrigerant
charging in heating
mode
2
Te s t o p e r a t i o n
in heating mode
3
Pump down
in heating
mode
4 Vacuum
5
Completion
Blank
Table 23. Button K2
Number of times
button K2 is
pressed Operation
7-segment display:
Digits 1 and 2
1 Refrigerant charging in cooling mode
2 Test operation in cooling mode
3 Pump down in cooling mode
4 Refrigerant detection operation
5Completion Blank
Table 24. Button K3
Number of times
button K3 is
pressed Operation 7-segment display
1
Initialize (reset)
operation
Same
as
power up: “8888”
Vista de página 40
1 2 ... 36 37 38 39 40 41 42 43 44 45 46 ... 51 52

Comentários a estes Manuais

Sem comentários