Trane VUVE Vertical Classroom Manual de Instalação Página 42

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 111
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 41
42 UV-SVN03F-EN
Installation—Electrical
Wiring
Motor data can be found in Table 5, p. 11.
Control Power. Unit ventilator controls and control
wiring can be factory mounted or field installed.
Wiring diagrams illustrate the standard unit motors with
one or more speed controls. Terminal wiring is provided
by Trane and the actual components used for a particular
installation may differ. Control and line diagrams for the
exact control system used are provided with each unit.
Electrical Wiring
Unit Wiring Diagrams. Specific unit wiring diagrams,
based on unit options ordered, are provided inside each
unit and can be easily removed for reference. Use these
diagrams for connections or trouble analysis. Wiring
diagrams are attached on the inside of the front panel of
the unit.
Supply Power Wiring. Refer to the unit nameplate to
obtain the minimum circuit ampacity (MCA) and
maximum fuse size (MFS) or maximum circuit breaker
(MCB) to properly size field supply wiring and fuses or
circuit breakers. Refer to the unit operating voltage listed
on the unit wiring schematic, submittal, or nameplate.
Reference the wiring schematic for specific wiring
connections.
Note: All field wiring should conform to NEC and all
applicable state and local code requirements. The
control panel box is always on the end opposite the
piping connections. Access the control box by
removing the two screws that secure the front
cover. This will allow the panel to be removed, to
provide access to the electrical components.
If the unit does not have a disconnect switch, the power
leads and capped ground wire are inside the control panel.
If the unit has a disconnect switch, the power leads are
wired to the junction box switch on the control panel. Pull
the capped ground wire into the junction box.
Electrical Grounding Restrictions. All sensor and
input circuits are normally at or near ground (common)
potential. When wiring sensors and other input devices to
the Tracer controller, avoid creating ground loops with
grounded conductors external to the unit control circuit.
Ground loops can affect the measurement accuracy of the
controller.
All input/output circuits (except isolated relay contacts and
optically isolated inputs) assume a grounded source,
either a ground wire at the supply transformer to control
panel chassis, or an installer supplied ground.
Wall-Mounted Control Interconnection Wiring. The
installer must provide interconnection wiring to connect
wall-mounted devices such as a fan mode switch or zone
sensor module. Refer to the unit wiring schematic for
specific wiring details and point-to-point wiring
connections. Dashed lines indicate field wiring on the unit
wiring schematics. All interconnection wiring must
conform to NEC Class 2 wiring requirements and any state
WARNING
Electrocution and Fire Hazards with
Improperly Installed and Grounded Field
Wiring!
Improperly installed and grounded field wiring poses
FIRE & ELECTROCUTION hazards. To avoid these
hazards, you MUST follow requirements for field wiring
installation and grounding as described in NEC and
your local/state electrical codes. All field wiring MUST
be performed by qualified personnel.
Failure to follow these requirements could result in
death or serious injury.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
NOTICE:
Equipment Damage!
Wiring diagrams provided in this manual are for
reference only. Actual wiring for particular options/
units could vary. Refer to the diagram provided on the
equipment for specific information. Failure to follow
recommendations above could result in premature
motor failures or equipment damage.
Do not remove or alter the wiring of the time delay
relay (DL). Failure to do so could result in equipment
failure.
WARNING
Fire Hazard!
When installing field provided controls, do not alter or
remove any built-in unit safeties. Tampering with unit
safeties could cause unit overheating and possible fire
hazard which could result in death or serious injury.
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types
of conductors. Failure to use copper conductors could
result in equipment damage.
UV-SVN03_.book Page 42 Thursday, January 24, 2013 5:27 PM
Vista de página 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 110 111

Comentários a estes Manuais

Sem comentários