Trane VUVE Vertical Classroom Manual de Instalação Página 9

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 111
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 8
General Information
UV-SVN03F-EN 9
Face and Bypass Actuator (Option). The face and
bypass damper actuator incorporates a direct couple
design. It provides electronic protection against overload.
A limit switch is not included, nor required as part of the
design. When reaching the damper end position, the
actuator automatically stops. The gears can be manually
disengaged with a button on the housing. Refer to Table 2,
p. 9 for face and bypass actuator specifications.
Modulating Water Valves (Option). The modulating
control valve provides optimum control of hot and chilled
water flow in various heating and cooling applications.
They are designed to provide sinusoidal valve actuator
travel and operate silently, resisting water hammer.
The actuator on the valve is a 24V, 3-point floating type.
Refer to Table 3 for modulating water valve specifications.
Isolation Valve (Option). The isolation valve is a two
position 24V, spring return type valve. It provides added
control in heating and cooling applications when used in
conjunction with the face and bypass damper.
On heating coils, and two-pipe changeover applications,
the valve is normally open to help prevent the coil from
freezing in-case of power loss.
For cooling, the valve is normally closed and opens when
there is a call for cooling. Refer to Table 4 , p. 9 for isolation
valve specifications.
Table 1. OA/RA actuator specification
Power supply 24 Vac ±20% 50/60 Hz
24 Vac ±10%
Power consumption Running: 2.5 W
Holding: 1 W
Transformer sizing 5 VA (class 2-power source)
Overload protection Electronic throughout 0° to 95° rotation
Control signal 2 to 10 Vdc
3-point floating with Trane controls
Angle of rotation Maximum 95°
Adjustable with mechanical stop
Torque 35 in·lb
Direction of rotation Spring return reversible with cw/ccw
mounting
Position indication Visual indicator, 0° to 95°
Noise level Running: 30 dB
Table 2. Face-bypass actuator specification
Table 3. Mod. water valve specification
Table 4. Isolation valve specification
Power supply 24 Vac ± 20% 50/60 Hz
24 Vac
± 10%
Power consumption 2 W
Transformer sizing 3 VA (class 2-power source)
Angle of rotation Maximum 95-degree
Adjustable with mechanical stop
Torque 35 in./lb
Direction of rotation Reversible with switch L/R
Position indication Clip-on indicator
Manual override External push button
Noise level Less than 35 dB
Control signal 3-point floating
Power supply 24 Vac - 50/60 Hz
Power consumption 4 W
Max. duty cycle 15%
Operating ambient temp. 0 to 65°C
32 to 150°F
Min./max. fluid temp. 1 to 95°C
34 to 203°F
Operating pressure
differential
Max. - 4 bar (60 psi)
Pressure rating Static - 20 bar (300 psi)
Burst - 100 bar (1500 psi)
Flow characteristic Linear
Power supply 24 Vac - 50/60 Hz
Power consumption 5 W
Max. fluid temp. 94°C
200°F
Min. fluid temp. 1°C
34°F
Max. operating pressure 300 psi
Max. close-off pressure 1/2 in. = 30 psi
3/4 in. = 20 psi
1 in. = 15 psi
UV-SVN03_.book Page 9 Thursday, January 24, 2013 5:27 PM