Coil Piping and Connections
Steam Coil Piping
Air handlers fitted with steam coils have labeled holes for piping penetrations. Figure 52 and
Figure 53 illustrate typical steam coil piping configurations. See Tabl e 2 for the codes of system
components in these figures.
The coil condensate return line must be piped full size of the condensate trap connection, except
for a short nipple screwed directly into the coil headers condensate return tapping. Do not bush
or reduce the coil return tapping size.
Table 2. Code of system components for piping figures
Code System component
FT Float and thermostatic steam trap
GV Gate valve
OV Automatic two-position (ON-OFF) control valve
VB Vacuum breaker
ST Strainer
AV Automatic or manual air vent
MV Modulating control valve
Figure 52. Typical piping for Type N steam coils and
horizontal tubes for horizontal airflow
Figure 53. Typical piping for Type NS steam coils and
horizontal tubes for horizontal airflow