
Installation
VAV-SVN09B-EN 11
New Facility VRRF Installation
(Non-Retrofit)
Note: When installing VRRF, make sure the controller is
level so the transducer can read airflow accurately.
Important: Make sure inlet and outlet ductwork are
adequately supported before installing
VRRF.
1. Before hanging VRRF, ensure that the VRRF will have a
minimum of 1.5 duct diameters of strait duct prior to
the inlet of the VRRF.
2. Hang theVRRF with straps (See Figure 1, p. 6 for Install
and Figure 2, p. 7 for weights)
3. Connect inlet ductwork to VRRF and screw in self
tapping screws.
4. Seal around flange of ductwork and VRRF with duct
sealant.
5. Connect outlet ductwork to VRRF and screw in self
tapping screws.
6. Seal around flange of ductwork and VRRF with duct
sealant.
7. After all connections are made , check to insure the
entire ductwork is air tight. Apply duct sealer as
necessary.
8. Cut to specifications on your unit, as shown in Figure 8
and Table 3. Cut “slits” in the insulation for the flow
tubes and brackets. Secure with duct tape. Encase
VRRF with insulation. See
Figure 7.
9. Use care not to damage the flow tubes when making
ductwork connections or insulating.
Specifications
UCM 4.2
Power Requirements
Supply: 18-32 VAC (24VAC nominal) at 50/60 Hz
Operating EnvironmentTemperature:
32 to 140 F (0-60 C)
Relative Humidity
10 to 90% non-condensing
Storage EnvironmentTemperature:
-40 to 150 F
Relative Humidity
10 to 90% non- condensing
Analog inputs
Space temperature
Thermistor
10 K ohms @77 F(25 C)
From 14 to 122 F (-10 to 50 C)
Space setpoint
Potentiometer
1K ohms
From 50 to 90 F (10 to 32.2 C)
Primary discharge air temperature
10 K ohms @77 F(25 C)
From -40 to 212 F (-40 to 100 C)
Primary airflow
Transducer
0-2in. water (0 to 498 Pa)
WARNING
Heavy Objects!
Ensure that all the lifting equipment used is properly
rated for the weight of the unit being lifted. Each of the
cables (chains or slings), hooks, and shackles used to
lift the unit must be capable of supporting the entire
weight of the unit. Lifting cables (chains or slings) may
not be of the same length. Adjust as necessary for even
unit lift. Other lifting arrangements could cause
equipment or property damage. Failure to follow
instructions above or properly lift unit could result in
unit dropping and possibly crushing operator/
technician which could result in death or serious injury.
Table 3. Insulation for RIRO
ABCD
Length
w/o
adapter
Length
w/
adapter
4" 21.5 16.75 10.75 5.25 17 19.5
5" 21.5 16.75 10.75 5.25 17 19.5
6" 21.5 16.75 10.75 5.25 17 19.5
8" 29.5 21.5 12.75 6.5 17 19.5
10" 36 25 15.75 7.5 17 19.5
12" 41.5 28 16.5 8 17 19.5
14" 47.5 32.75 18.25 9.5 17 19.5
16" 56 35.5 18.75 9.25 17 19.5
Figure 8. Insulation cut measurements
Table 3. Insulation for RIRO
ABCD
Length
w/o
adapter
Length
w/
adapter
Comentários a estes Manuais