Installation
44 VAV-SVN09B-EN
To Set the Measured Value for Airflow
1. Expand the ‘VAV Setup’ group
2. Choose the desired settings from the ‘VAV Setup’
group
3. Click the ‘Save’ button
Actuator Mounting
Trane offers a factory-mounted actuator with a 90-second
drive time.The actuator drives 1 degree per second. A
field-installed actuator may be used if desired. Actuator
shaft is ½” diameter and designed to travel clockwise to
close damper and counter-clockwise to open damper.The
indicator on the end of actuator shaft can be used to
determine position of damper.
Control Airflow Setup
1. Connect Magnahelic to "T" ports on pneumatic tubing
connected from Flow Rings toTransducer.
2. Connect to controller with Rover™orTU service tool
3. Recalibrate VAV unit
4. Open up VAV damper to Max Flow and measure the
airflow
across the magnahelic.
5. Take the reading and compare it to chart on side of
VRRF
unit to get CFM value.
6. Now that you have the CFM, compare the CFM value of
the
chart on the unit to the FlowValue on the controller
that is shown in Rover orTU on the VAV Status menu.
If they are different adjust the controller to the correct
value.
Figure 40. UC400 and UC210 configuration: set measure value for airflow
NOTICE:
Equipment Damage!
When installing or replacing the actuator, tighten the
actuator set screw per the manufacturers instructions.
Failure to follow the manufacturer’s specifications may
result in unit malfunction.
Figure 41. Unit chart