
VAV-SVN09B-EN 5
General Information
This manual describes the installation of the Round In
Round out (VRRF) VAV units with mounting and
recommended wiring of the VRRF units.
For controls setup and operation parameters, reference
the following literature:
• UCM 4.2: VAV-SVX01*-EN
• VV550: CNT-SVX17*-EN
• UC400: VAV-SVX07*-EN
• UC210: BAS-SVX62*-EN
The VRRF can be used in new installations as well as
retrofitting older style units.
Note: Not all older-style Trane VAV units can be
retrofitted with the VRRF and should be
researched before ordering the VRRF on a case-
by-case basis.
The VRRF can be ordered with or without DDC controls. If
ordered with controls, the unit would have either a UCM
4.2, VV550 or UC400/UC210 DDC control module.
The controls will be factory mounted to the RIRO damper
and field installed to existing system. How this installation
takes place will be dependent on if it is a new installation
or if the unit is being retrofitted to a pre-existing unit type.
Receiving and Handling
The unit may be shipped from the factory in a number of
different ways. Upon receiving the equipment, complete
the following:
• Locate the nameplate and refer to the model and sales
order number and check that the correct units have
been delivered.
• Check that the facility can provide the correct voltage to
the unit according to the name plate.
• Inspect the control enclosure if applicable and the air
damper casing for dents or punctures.
• Verify the options have been included, such as
controls, water valve, adapters, and relays kits which
include wiring harnesses.
• Manually rotate the damper actuator to assure that
there are no obstructions within the housing.
• Claims for in-transit damage must be filed
immediately with the delivery carrier.
• Locate and verify that the correct zone sensors are with
the order.These will be marked with an orange
“Accessories Enclosed” label. Store in a secure
location until needed. Accessories lost at the jobsite
are NOT covered byTrane’s warranty.
• If a discrepancy occurs between what was ordered and
what is received, contact you localTrane
representative immediately.
• Read the appropriate section in this manual for
installation procedures prior to actual starting of
equipment.
Upon receiving the equipment, please inspect each unit
and components for external or internal damage. Refer to
the bill of lading to insure all equipment and accessories
have been received. Contact your localTrane sales
representative and notify the trucking company
immediately of any short ship or damaged equipment.
Unit Information
The basic unit consists of a sheet metal casing with an air
damper which is used to modulate the air being delivered
into the occupied zone.The unit is designed to modulate
either cooling or heating air between the temperatures of
40 and 140 degrees F. Primary air enters the air valve
through its round inlet and sent into the air valve cylinder
and exits from the round outlet.This air could be sent strait
to the diffusers or in conjunction with a VAV unit that is
being retrofitted.
The basic unit can be ordered for vertical or horizontal
airflow.The options for a basic unit that are available are
power fuse, transformer, disconnect, adapter, DDC
controller, and Wireless Zone sensor. Other options
available if retrofitting electric heat or hot water units
would be relay kits to support the control of electric heat
strips.We can also include two-position or modulating hot
water valves for control of hot water in the reheat coil.
When looking to retrofit a fan powered unit, you could also
order the relay kit(s) with the wiring harness as an option.
All types of DDC controllers for theVRRF have 24VAC triac
outputs.The UC400 and UC210 also have relay-based
binary outputs.The outputs are available for retrofitting a
single duct or a fan-powered unit. A single-duct unit could
use the outputs available to control three (3) stages of
electric heat, modulating hot water valve or two position
hot water valve. For a fan-powered unit, the controller
would use one output for the fan and the other two to
control two stages of electric heat. If it had a hot water coil,
then the two extra outputs could be used to control a
modulating hot water valve or a two-position hot water
valve.These re-heat units are used primarily to reheat air-
to-zone temperature when the load in the occupied space
is low. Primary air is modulated through the VariTrane™
air valve by rotating the damper blade. All air valves have
a round inlet for easy fit-up with incoming ductwork.
Agency Listings Compliance
• UL listed
• AHRI 880 certified
Comentários a estes Manuais