Installation
8 VAV-SVN09B-EN
No hanger brackets are provided on these units since the
unit should be supported by means of a hanger strap.The
hanger strap should be secured to the unit casing as
shown in Figure 1, p. 6.
Unit Accessibility
VRRF does not provide internal access, as all functioning
components are external to the unit.
Clearances
For proper service it is recommended that 36" side
clearance be provided for service and access. It is also
recommended that 6" of top and bottom clearance be
provided.
The minimum clearance for the controls is 36".
NEC and/or local codes overrides all clearance
requirements.
Duct Connections Installation
All VRRF units should have a minimum of 1.5 duct
diameters of straight duct prior to the inlet of the VRRF.
This is to allow accurate reading from the flow ring.The
outlet connection is dependent on a number of factors.
The main factor is your application. If the VRRF is used as
a new installation, then you connect the outlet of theVRRF
to the ductwork. If it is a retrofit of an existing unit, then it
depends upon what type of unit you are looking to replace.
(Table 1and Table 2 show the different styles of units and
the possible outlet connection. When determining which
of these two tables to use, reference the fourth digit in
Model Number of the existing VAV unit.)
Table 1. C, D, or E style units
(a)
(a) C, D, E digit is found in the 4th digit of model number
Controls Air Valve Type
Outlet
Connection
Type
Pneumatic Normally Closed
Single Duct
Elec. Heat
Retrofit not
possible
(b)
(b) When retrofit not possible, replace the existing unit.
Pneumatic Normally Closed
Parallel Fan
Elec. Heat
Retrofit not
possible
(b)
Pneumatic Normally Closed All Others 1
Pneumatic Normally Open
Single Duct
Elec. Heat
2
Pneumatic Normally Open
Parallel Fan
Elec. Heat
2
Pneumatic Normally Open All Others 1 & 2
Analog Normally Open
Single Duct
Elec. Heat
2
Analog Normally Open
Parallel Fan
Elec. Heat
2
Analog Normally Open All Others 1 & 2
DDC Normally Open
Single Duct
Elec. Heat
2
DDC Normally Open
Parallel Fan
Elec. Heat
2
DDC Normally Open All Others 1 & 2
Notes:
1. Adapter design (Remove Old Air Valve and replace with Adapter for
RIRO)
2. Standard RIRO unit (Drive valve to max. and install RIRO upstream
of unit.)
Table 2. F style units
(a)
(a) F digit is found in the 4th digit of model number
Controls Air Valve Type
Outlet
Connection
Type
Pneumatic Normally Closed All 2
Analog Normally Open All 2
DDC Normally Open All 2
Notes:
1. Standard RIRO unit (Drive valve to max. and install RIRO upstream of
unit.)
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
WARNING
Heavy Objects!
Ensure that all the lifting equipment used is properly
rated for the weight of the unit being lifted. Each of the
cables (chains or slings), hooks, and shackles used to
lift the unit must be capable of supporting the entire
weight of the unit. Lifting cables (chains or slings) may
not be of the same length. Adjust as necessary for even
unit lift. Other lifting arrangements could cause
equipment or property damage. Failure to follow
instructions above or properly lift unit could result in
unit dropping and possibly crushing operator/
technician which could result in death or serious injury.
WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the
insulation in this product during installation,
maintenance or repair will expose you to airborne
particles of glass wool fibers and ceramic fibers known
to the state of California to cause cancer through
inhalation. You MUST wear all necessary Personal
Protective Equipment (PPE) including gloves, eye
protection, mask, long sleeves and pants when
working with products containing fiberglass wool.
Exposition to glass wool fibers without all necessary
PPE equipment could result in cancer, respiratory, skin
or eye irritation, which could result in death or serious
injury.