Installation
VAV-SVN09B-EN 13
Analog Inputs
• AI1
• Space temperature; thermistor: 10k @77°F (25°C)
• Range: 32°F to 122°F (0°C to 50°C)
• AI2
• Space setpoint; potentiometer: 1k
• Range: from 50°F to 90°F (10°C to 32.2°C), */**
(thumbwheel) functionality supported
• AI3
• Spare
• AI4
• Discharge air temperature: 10k @77°F (25°C)
• Range: from -40°F to 212°F (-40°C to 100°C)
• AI5
• Supply air temperature: 10k @77°F (25°C)
• Range: from -40°F to 212°F (-40°C to 100°C)
Universal Inputs
• UI1;
• Spare, but recommended for relative humidity
• Resistive/thermistor inputs: 0-10 Vdc inputs or 4-20
mA inputs
• Current Mode Impedance: 200 , Voltage Mode
Impedance: 10k minimum
• UI2;
• Provided point for CO
2
• Resistive/thermistor inputs: 0-10 Vdc inputs or 4-20
mA inputs
• Current Mode Impedance: 200 , Voltage Mode
Impedance: 10k minimum
Pressure Inputs
•P1
• Supply airflow, pressure transducer
• From 0 to 2 in. water column (0 to 498 Pa)
•P2
• Spare (recommended for dual duct secondary
airflow)
Binary Inputs
• BI1
• Occupancy
• BI2
• Spare
• BI3
• Spare
Binary Outputs
Analog Outputs
•AO1
• Spare output.
• Voltage output is 0 to 10 Vdc, 500 minimum
impedance.
• Current output is 4-20 mA, 500 max. impedance.
• Also can output 100 Hz PWM signal for control of a
Trane fan-powered ECM fan setpoint signal to the
EC motor.
•AO2
• Spare.
• Voltage output is 0 to 10 Vdc, 500 minimum
impedance.
• Current output is 4-20 mA, 500 maximum
impedance.
• Also used onTrane VAV units for SCR electric heat
0-to-10 Vdc modulation control.
Note: For more information on wiring spare points, refer
to theTracer UC400 Programmable Controller
Installation, Operation, and Maintenance Manual
(BAS-SVX20).
UC210
Binary
Outputs
Type
Output
Rating
Pilot duty
BO1 Fan 10A up to 277 Vac
10A at 30 Vac/VDC, 2A at
120 Vac, 8 A at 250 Vac
BO2 Spare Relay 10A up to 277 Vac
10A at 30 Vac/VDC, 2A at
120 Vac, 8 A at 250 Vac
BO3 Spare Relay 10A up to 277 Vac
10A at 30 Vac/VDC, 2A at
120 Vac, 8 A at 250 Vac
BO4 Fan ON/Off
24-27 Vac, 0.5A
Resistive VA
BO5 Heat stage 3 TRIAC
24-27 Vac, 0.5A
Resistive VA
BO6
Heat stage 2/Water
Valve Close TRIAC
24-27 Vac, 0.5A
Resistive VA
BO7
Heat stage 1/Water
Valve Open TRIAC
24-27 Vac, 0.5A
Resistive VA
BO8
Air Damper Close
TRIAC
24-27 Vac, 0.5A
Resistive VA
BO9
Air Damper Open
TRIAC
24-27 Vac, 0.5A
Resistive VA
Table 5. UC400 specifications
Storage
Temperature: -40 to 185°F (-40 to 85°C)
Humidity: 5% to 95% (non-condensing)
Operating
Temperature: -40 to 185°F (-40 to 85°C)
Humidity: 5% to 95% (non-condensing)
Input Voltage:
20.4-27.6 Vac, (24 Vac± 15% nominal), 50-60
Hz, 10.5 VA plus 1 VA per 20mA of 24 VDC load
plus 12 VA maximum per binary load